Switchboard cabinet - ZAT

3. 9. 2013

The subject of tests were two separate enclosures.

1) Vibration test according to EN 60068-2-6

Dimensions (WxDxH) 800x1000x2100, estimated weight of about 295 kg, power consumption 800VA

Dimensions (WxDxH) 800x800x2100, estimated weight of about 250 kg, power consumption 800VA

Frequency range 10 ÷ 500 Hz, constant acceleration of 10 m/s2

2) Test for rapid temperature changes (use of two temperature chambers) according to EN 60068-2-14

Lower temperature Ta = -25 ° C
Higher temperature Tb = +70 ° C
Number of test cycles = 5

Do you need assistance with testing?